Kohler 50 kW Residential Generators
Prime Ratings: |
|
35 kW (44 kVa) |
|
Standby Ratings: |
|
40 kW (50 kVa) |
|
Hertz: |
|
50 Hz |
|
Alternator Type: |
|
Brushless, Permanent-Magnet |
|
Engine Manufacturer: |
|
General Motors |
|
Engine Model: |
|
Industrial Powertrain Vortec 5.0L |
|
Cylinder Arrangement: |
|
V-8 |
|
Max Power at Rated RPM: |
|
54.5 kWm (73 BHP) |
|
Prime Fuel Consumption at |
|
|
100% load: |
|
6.6 m³/hr (233 cfh) |
75% load: |
|
5.3 m³/hr (187 cfh) |
50% load: |
|
4 m³/hr (143 cfh) |
25% load: |
|
2.9 m³/hr (101 cfh) |
|
Standby Fuel Consumption at |
|
|
100% load: |
|
7.2 m³/hr (254 cfh) |
75% load: |
|
5.7 m³/hr (202 cfh) |
50% load: |
|
4.3 m³/hr (153 cfh) |
25% load: |
|
3 m³/hr (105 cfh) |
Kolher 50kW Spec Sheet
|
LP or Natural Gas
-
Kohler Co. provides one-source responsibility for the generating system and accessories.
-
The generator set and its components are prototype-tested, factory-built ,and production-tested.
-
The generator set accepts rated load in one step.
-
Safer Power for Sensitive Electronics
-
A one-year limited warranty covers all systems and components. Two- and five-year extended warranties are also available.
Alternator features:
- The unique Fast-Response(TM) II excitation system delivers excellent voltage response and short circuit capability using a permanent magnet (PM)-excited alternator.
- The brushless, rotating-field alterantor has broadrange reconnectability.
- NEMA MG1 ,IEEE, and ANSI standards compliance for temperature rise and motor starting.
- Sustained short-circuit current of up to 300% of the rated current for up to 10 seconds.
- Sustained short-circuit current enabling down stream circuit breakers to trip without collapsing the alternator field.
- Self-ventilated and dripproof construction.
- Vacuum-impregnated windings with fungus-resistant epoxy varnish for dependability and long life.
- Superior voltage waveform from a two-thirds pitch stator and skewed rotor.
- Fast-Response(TM) II brushless alternator with brushless exciter for excellent load response.
Other features:
- A rugged industrial gas engine delivers rated power at 1800 rpm (60 Hz) and 1500 rpm (50 Hz).
- Controllers are available for all applications. See controller features inside.
- The electronic, isochronous governor incorporates an integrated drive-by-wire throttle body actuator delivering precise frequency regulation.
|